Model Number: UBR-1000Va
Key Specifications/Special Features:
Output:Power levels: 800VA/480W, 1100VA/660WOutput voltage: 100/110/115/120V selectableVoltage waveform: sine waveCrest factor: 3:1Output frequency: auto select for 50/60Hz, 47-55Hz for 50Hz nominal, 56-65 for 60Hz nominalRegulation (nominal): ±5% typical of nominal voltage (optional at ±8% AVR for wide I/P up to ±35%)Regulation: ±3% of selected output voltage (battery mode, adjustable with the remote set-up software)Transfer time: blackout 3ms typical, brownout 1ms typical, battery mode to normal mode: 1ms typicalOver current protection: over load alarm level 100-120%, over load shutdown level 120-190% (adjustable by using the remote set-up software)Input:Nominal voltage: 100/110/115/120V selectable
Input frequency: 47-65Hz, 50/60Hz auto-sensing
Efficiency: 97% (normal mode)
Noise filtering: full time EMI/RFI filtering
Over current protection: by AC fuse
Voltage range: -20 to +24% for rated voltage (adjustable with the remote set-up software)
AVR range (2 bucks, 2 boosts):
Enhanced buck: +15% of rated voltage, buck mode: +5% of rated voltage
Boost mode: -5% of rated voltage, enhanced boost: -12.5% of rated voltage
Surge protection: 216 joules
Battery:
Battery type/voltage: maintenance-free sealed, valve-regulated, Lead-acid: 6V 9Ahx3 (18V DC), 6V 9Ahx4 (24V DC)
Backup time: 12 minutes at 1/2 load, 4 minutes at full-load typically
Charging time/current: <3 hours to 90% at normal status, 2.5A (average with 2 charging modes)
Protection: over current protection and over charging voltage protection (SCR control), thermal protection (CPU control), when temperature inside USP is over 45°C, charger will stop charging for 2.5 minutes followed by an 1.5 minutes charging the cycle will be repeated until the temperature is lower than 44°C
Monitoring: smart monitoring and warning for failed battery or open-circuit battery
Auto-detection each time when power on or every 6 days
Communications and management:
Standard interface port: UPSilon2000 compatible RS232, USB, SNMP (external type)
Optional interface part: DB9
Control panel: LCD or LED
Audible alarm: alarm on battery: low battery and battery over voltage, alarm on abnormal operation: over load, short-circuit and over heat
EBT system: supports for LCD display (estimation of backup time)
Green mode function: 1 to 14% of full load (adjustable with the remote set-up software), default=off
Environmental and safety:
Operating temperature: up to 1500 meters: 0 to 40°C (32 to 104°F)
Transit/storage temperature: -15 to 55°C (5 to 131°F)
Relative humidity: 5-95% non condensing